Sample Home Inspection Report
Date: 7/22/2011 | Time: | Report ID: |
Property: 16 Vicksburg Ln. Travelers Rest S.C. 29690 |
Customer: John Customer |
Real Estate Professional: Angela Agent Red Roof Realty |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Standards of Practice: NACHI National Association of Certified Home Inspectors | In Attendance: Customer Agent | Type of building: Single Family (1 story) |
Approximate age of building: Under 5 Years | Home Faces: NE | Temperature: Over 90 |
Weather: Cloudy | Ground/Soil surface condition: Dry, Wet | Rain in last 3 days: No |
Radon Test: No | Water Test: No |
Roof Covering: Architectural | Viewed roof covering from: Ground | Chimney (exterior): N/A |
Inspection Items |
1.0 | ROOF COVERINGS Comments: Inspected | |||
The roof covering, its flashings, and penetrations appeared to be in
good condition at time of inspection.
|
1.1 | FLASHINGS Comments: Inspected |
1.2 | SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS Comments: Inspected |
1.3 | ROOF DRAINAGE SYSTEMS Comments: Inspected | |
The gutter system appeared to be in good functional order at time of
inspection.
|
Siding Style: Lap | Siding Material: Composite board | Exterior Entry Doors: Wood Insulated glass |
Appurtenance: Covered porch Sidewalk Covered patio | Driveway: Concrete |
Inspection Items |
2.0 | WALL CLADDING FLASHING AND TRIM Comments: Inspected | ||
The siding and trim looked good. The exterior paint appears to be
holding up good as well.
|
2.1 | DOORS (Exterior) Comments: Inspected |
2.2 | WINDOWS Comments: Inspected |
2.3 | DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/ COVER AND APPLICABLE RAILINGS Comments: Inspected |
2.4 | VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYS AND RETAINING WALLS (With respect to their effect on the condition of the building) Comments: Inspected |
2.5 | EAVES, SOFFITS AND FASCIAS Comments: Inspected |
Garage Door Type: One automatic | Garage Door Material: Insulated Light inserts Metal | Auto-opener Manufacturer: LIFT-MASTER |
Inspection Items |
3.0 | GARAGE CEILINGS Comments: Inspected | ||
The garage ceiling appeared to be in good shape.
|
3.1 | GARAGE WALLS (INCLUDING FIREWALL SEPARATION) Comments: Inspected | |||
The garage walls and floor appeared to be in good shape, however as
you can see there is a lot of area that was obscured by personal
items which makes it hard to visually inspect.
|
3.2 | GARAGE FLOOR Comments: Inspected |
3.3 | GARAGE DOOR (S) Comments: Inspected | |||
The garage door, its windows, insulation, and bottom seal appeared
to be in good condition at time of inspection.
|
3.4 | OCCUPANT DOOR FROM GARAGE TO INSIDE HOME Comments: Inspected |
3.5 | GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance) Comments: Inspected |
The garage did reverse good when met with resistance. Note this is a simple adjustment that can be made to take more or less resistance depending on the home owners preference. |
Ceiling Materials: Sheetrock | Wall Material: Sheetrock | Floor Covering(s): Carpet Hardwood T&G Tile |
Interior Doors: Raised panel Wood | Window Types: Thermal/Insulated | Window Manufacturer: UNKNOWN |
Cabinetry: Wood | Countertop: Granite |
Inspection Items |
4.0 | Complimentary view Comments: Inspected | ||||
A complementary view shows how well kept the home is and some
of its lay out, however it also shows just how much visual inspection
of floors an walls are obscured by personal items.
|
4.1 | CEILINGS Comments: Inspected |
4.2 | WALLS Comments: Inspected |
4.3 | FLOORS Comments: Inspected |
4.4 | STEPS, STAIRWAYS, BALCONIES AND RAILINGS Comments: Inspected |
4.5 | COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS Comments: Inspected |
4.6 | DOORS (REPRESENTATIVE NUMBER) Comments: Inspected |
4.7 | WINDOWS (REPRESENTATIVE NUMBER) Comments: Inspected |
Foundation: Poured concrete | Method used to observe Crawlspace: No crawlspace | Floor Structure: Slab |
Wall Structure: 2 X 4 Wood | Ceiling Structure: 2X4 | Roof Structure: Engineered wood trusses |
Roof-Type: Gable Hip | Method used to observe attic: Walked | Attic info: Attic access |
Inspection Items |
5.0 | FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.) Comments: Inspected |
5.1 | WALLS (Structural) Comments: Inspected |
5.2 | COLUMNS OR PIERS Comments: Inspected |
5.3 | FLOORS (Structural) Comments: Inspected |
5.4 | CEILINGS (structural) Comments: Inspected |
5.5 | ROOF STRUCTURE AND ATTIC Comments: Inspected | |||
The roof structure in the attic appeared to be in good sound condition
with no apparent leaks at time of inspection.
|
Water Source: Public | Plumbing Water Supply (into home): Pex | Plumbing Water Distribution (inside home): PEX |
Washer Drain Size: 2" Diameter | Plumbing Waste: PVC | Water Heater Power Source: Gas (quick recovery) |
Water Heater Capacity: 50 Gallon (2-3 people) | Manufacturer: RHEEM | Water Heater Location: Garage |
Inspection Items |
6.0 | PLUMBING DRAIN, WASTE AND VENT SYSTEMS Comments: Inspected |
No leaks found at time of inspection. |
6.1 | PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES Comments: Inspected |
This home has nice fixtures and they all appeared to be working fine with no leaks at time of inspection. |
6.2 | HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS Comments: Inspected | |
The hot water heater was working fine at time of inspection.
|
6.3 | MAIN WATER SHUT-OFF DEVICE (Describe location) Comments: Inspected | ||
The main cut off is at the meter located in the front yard and as in all
newer houses there is a cut off and regulator in the garage near the
hot water heater.
|
6.4 | FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting, supports, leaks) Comments: Inspected |
6.5 | MAIN FUEL SHUT OFF (Describe Location) Comments: Inspected | |
The main fuel cut off is located at the meter on the right side of the
home.
|
Electrical Service Conductors: Below ground | Panel capacity: 200 AMP | Panel Type: Circuit breakers |
Electric Panel Manufacturer: SQUARE D | Branch wire 15 and 20 AMP: Copper | Wiring Methods: Romex |
Inspection Items |
7.0 | SERVICE ENTRANCE CONDUCTORS Comments: Not Inspected |
Below ground |
7.1 | SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND DISTRIBUTION PANELS Comments: Inspected | ||
The main electrical panel appeared to be in good order at time of
inspection and clearly labeled.
|
7.2 | BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE Comments: Inspected |
7.3 | CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls) Comments: Inspected |
7.4 | POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIOR PLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT, EXTERIOR WALLS OF INSPECTED STRUCTURE Comments: Inspected |
7.5 | OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) Comments: Inspected |
7.6 | LOCATION OF MAIN AND DISTRIBUTION PANELS Comments: Inspected |
7.7 | SMOKE DETECTORS Comments: Inspected |
7.8 | CARBON MONOXIDE DETECTORS Comments: Not Present |
I did not see any carbon monoxide detectors, however I recommend added when gas heat and gas logs are in use. |
Heat Type: Forced Air | Energy Source: Gas | Number of Heat Systems (excluding wood): One |
Heat System Brand: TEMPSTAR | Ductwork: Insulated | Filter Type: Disposable |
Filter Size: 20x20 | Types of Fireplaces: Non-vented gas logs | Operable Fireplaces: One |
Cooling Equipment Type: Air conditioner unit | Cooling Equipment Energy Source: Electricity | Central Air Manufacturer: TEMPSTAR |
Number of AC Only Units: One |
Inspection Items |
8.0 | HEATING EQUIPMENT Comments: Inspected | |
The heat side of the HVAC preformed well at time of inspection.
|
8.1 | NORMAL OPERATING CONTROLS Comments: Inspected |
8.2 | DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units and convectors) Comments: Inspected |
8.3 | PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM Comments: Inspected |
8.4 | CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) Comments: Inspected |
8.5 | SOLID FUEL HEATING DEVICES (Fireplaces, Woodstove) Comments: Inspected |
8.6 | GAS/LP FIRELOGS AND FIREPLACES Comments: Not Inspected |
I am not allowed to operate gas logs when the pilot is not lit at time of inspection. |
8.7 | COOLING AND AIR HANDLER EQUIPMENT Comments: Inspected | |||
There was about a 17 degree differential between the return and the
processed air coming out of the registers. Given the conditions of 93
degrees exterior,130 degrees in the attic, and all the duct work is
overhead I believe the air conditioning unit was preforming good.
|
8.8 | NORMAL OPERATING CONTROLS Comments: Inspected |
8.9 | PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM Comments: Inspected |
Attic Insulation: Blown | Ventilation: Ridge vents | Exhaust Fans: Fan with light |
Dryer Power Source: 220 Electric | Dryer Vent: Flexible Vinyl | Floor System Insulation: NONE |
Inspection Items |
9.0 | INSULATION IN ATTIC Comments: Inspected | ||
The insulation in the attic is good.
|
9.1 | INSULATION UNDER FLOOR SYSTEM Comments: Not Present |
9.2 | VENTILATION OF ATTIC AND FOUNDATION AREAS Comments: Inspected |
9.3 | VENTING SYSTEMS (Kitchens, baths and laundry) Comments: Inspected |
Dishwasher Brand: BOSCH | Disposer Brand: UNKNOWN | Exhaust/Range hood: GENERAL ELECTRIC |
Range/Oven: GENERAL ELECTRIC | Built in Microwave: GENERAL ELECTRIC |
Inspection Items |
10.0 | DISHWASHER Comments: Inspected |
10.1 | RANGES/OVENS/COOKTOPS Comments: Inspected |
10.2 | RANGE HOOD Comments: Inspected |
10.3 | FOOD WASTE DISPOSER Comments: Inspected |
10.4 | MICROWAVE COOKING EQUIPMENT Comments: Inspected |
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To CURTIS HOME INSPECTION, INC.
INVOICE |
CURTIS HOME INSPECTION, INC.
2072 Keeler Mill Rd Greenville S.C. 29617 864-444-2944 Inspected By: CURTIS F. MCCLURE |
Inspection Date: 7/22/2011
Report ID: |
Customer Info: | Inspection Property: |
John Customer
Customer's Real Estate Professional: Angela Agent Red Roof Realty |
16 Vicksburg Ln. Travelers Rest S.C. 29690 |
| ||||||||
Tax $0.00 | ||||||||
Total Price $275.00 |
Payment Method:
Payment Status:
Note:
Inspection Contract Agreement
This contract is an agreement between the client listed below , CURTIS HOME INSPECTION INC.,to perform an inspection of the home or building listed below according to the "Standards of Practice" of the South Carolina L.L.R.. These standards of practice inform you of what a home inspector should report, and what is not expected of the home inspector to report. This inspection is a limited visual inspection as a generalist. Areas that are inaccessible are not part of this inspection including but not limited to: behind walls, furniture, under rugs, inaccessible areas and below soil. The client signing below assumes all risk for potential problems or conditions including those areas not accessible by the inspector. The Client assumes all risk for problems noted in this report that may reveal further damage during a repair or further investigation by a qualified professional. Your signature below is your acceptance of these terms and conditions. A home inspection is not technically exhaustive and the inspector does not dismantle or perform testing that is destructive. The inspector is limited by this inspection agreement and cannot be expected to find or discover all defects in this building.
The purpose and scope of this inspection is to provide you with a better understanding of the property's condition as observed at the time of the home inspection. It will include an inspection of: Structural Components, Exterior, Roofing, Plumbing, Electrical, Heating, Central Air Conditioning, Interiors, Insulation, Ventilation and built-in kitchen appliances.
Our inspection does not include the inspection or any part of testing or determining whether or not these conditions exist such as: Asbestos, Formaldehyde, Mold or Fungi, or bio-aerosols. Soil or geological conditions. Pools and or equipment related to pools, spas or jacuzzis. Pests or Termites or wood eating insects. Elevators, solar systems. Refrigeration units, water filtration units, security alarms, intercoms, phone, cable, satellite, window treatments or mini-blinds, oven clocks or timers or clean feature, central vacuum solar systems or lightning arrestors. This inspection does not include a test on "Synthetic Stucco" as this is a separate test and contract. CURTIS HOME INSPECTION, INC. will not operate heating or cooling systems in temperatures that may cause damage to the unit. Air conditioning system will not be operated by CURTIS HOME INSPECTION, INC. in outside temperatures of 65 degrees or less. We do not inspect heat exchanger for cracks. Plumbing and electrical must be turned "on" for the inspection of these areas and components. Well or spring systems, pressure, depth, water level or condition is not part of this inspection. Furnaces, must be "on" or capable of being turned on by using normal operating controls. Pilot lights must be "lit" in order to inspect these components or systems (i.e. gas fireplace, wall heaters). Septic field inspections are not inspected and are not part of this contract. CURTIS HOME INSPECTION, INC. Inspection does not inspect for code compliance or ordinances. This inspection does not include detached buildings or garages.
The home inspection report is an " opinion" of CURTIS HOME INSPECTION, INC.. Our interpretation of what is good or fair, may be different than yours. You are encouraged to be present at the time of your inspection so we will both have an understanding of each others perception. The client accepts responsibility for incomplete information if the Client did not attend the inspection. Our purpose is to determine whether or not a system or component (electrical, heating, visible structure etc) is functioning for which it was intended. We are not responsible to determine all that may be wrong with that system or component, just whether or not a second opinion is needed, such as a licensed electrician or HVAC contractor, or any specialist for that field or trade. They determine what steps are necessary to correct. Their troubleshooting may reveal additional items not mentioned in this report. Any item mentioned in the report may need additional inspections by other qualified specialists. It is up to the Client who will be the person signing this contract to seek qualified specialists to investigate further any item or component that is commented on in the inspection report before closing. We are not responsible for items mentioned in this report. We are not a guarantee nor do we guarantee any items or opinions described on this report. This inspection is to reduce the risk of finding a potential problem, not to eliminate them. We are not a home warranty company nor do we carry insurance on warranty claims. The limited liability of the inspector and CURTIS HOME INSPECTION, INC. and the inspection report to the Client, spouse, executors or heirs or administrators are limited to a refund of the fee paid for the inspection and report.
By payment of our fee and the Client's signature, the Client acknowledges and understands and agrees to the statements and terms contained herein, and will hold CURTIS HOME INSPECTION, INC. and myself harmless to any claims made. The Client, spouse, executors or heirs or administrators are limited to a refund of the fee paid for this inspection and report. This limitation applies to anyone who claims damages or expenses of any kind incurred due to the errors or omissions in this inspection and report.
The cost of the home inspection is based upon heated square footage of the home to be inspected. Payments must be made at the time of inspection. CURTIS HOME INSPECTION, INC. agrees to provide you with a report within three business days or sooner by providing your email address.
CURTIS HOME INSPECTION, INC. MUST RECEIVE A COPY OF THIS AGREEMENT SIGNED BY THE CLIENT BEFORE THE INSPECTION CAN BEGIN.
Does the clients Realtor or real estate
agency, have permission to receive a copy of this report? Dose the Seller have permission to receive a copy
of |
Location:
16 Vicksburg Ln. Travelers Rest S.C. 29690 Date: 7/22/2011 Inspector: CURTIS F. MCCLURE Total Inspection Cost: $275.00 |
PDF Copy of Home Inspection Report
S.C. RBI 2620
Contact
864-444-2944
Curtis@CurtisHI.com
Who We Serve
- Home Buyers
- Home Sellers
- Investment Buyers
- Investment Sellers
- Investment Renters
- Financial Companies
- Insurance Companies
- Home Builders
- Real Estate Companies